框架脱扣器默认值设定
<h3>- 说明</h3>
<p><strong>In:表示订货规范中的额定电流字段;
0.8In:表示0.8倍额定电流值,乘法关系;
</strong></p>
<hr />
<p><strong>脱扣器类型:PTU2.1/PTU4.1/PTU4.2/PTU6.1/PTU6.2</strong></p>
<table>
<thead>
<tr>
<th>序号</th>
<th>字段名称</th>
<th>单位</th>
<th>下界</th>
<th>上界</th>
<th>默认值</th>
<th>上级字段</th>
</tr>
</thead>
<tbody>
<tr>
<td>1</td>
<td>Ir</td>
<td>A</td>
<td>0.4In</td>
<td>1In</td>
<td>1In</td>
<td>过载长延时保护</td>
</tr>
<tr>
<td>2</td>
<td>tr</td>
<td>s</td>
<td>8s</td>
<td>960s</td>
<td>60s</td>
<td>过载长延时保护</td>
</tr>
<tr>
<td>3</td>
<td>Isd</td>
<td>A</td>
<td>1.5Ir</td>
<td>15Ir</td>
<td>3Ir</td>
<td>短路短延时保护</td>
</tr>
<tr>
<td>4</td>
<td>Tsd</td>
<td>s</td>
<td>0.1s</td>
<td>0.4s</td>
<td>0.1s</td>
<td>短路短延时保护</td>
</tr>
<tr>
<td>5</td>
<td>Ii</td>
<td>A</td>
<td>1In</td>
<td>20In</td>
<td>6In</td>
<td>短路瞬时保护</td>
</tr>
<tr>
<td>6</td>
<td>Ig</td>
<td>A</td>
<td>0.2In</td>
<td>1In</td>
<td>0.8In/1200A</td>
<td>接地保护</td>
</tr>
<tr>
<td>7</td>
<td>tg</td>
<td>s</td>
<td>0.1s</td>
<td>100s</td>
<td>0.8/3s</td>
<td>接地保护</td>
</tr>
<tr>
<td>8</td>
<td>δ</td>
<td>%</td>
<td>\</td>
<td>\</td>
<td>80%</td>
<td>电流不平衡保护</td>
</tr>
<tr>
<td>9</td>
<td>tδ</td>
<td>s</td>
<td>\</td>
<td>\</td>
<td>3s</td>
<td>电流不平衡保护</td>
</tr>
<tr>
<td>10</td>
<td>In</td>
<td>A</td>
<td>0.5A</td>
<td>30A</td>
<td>0.5A</td>
<td>剩余电流保护</td>
</tr>
<tr>
<td>11</td>
<td>tn</td>
<td>s</td>
<td>0.006s</td>
<td>0.83s</td>
<td>0.83s</td>
<td>剩余电流保护</td>
</tr>
<tr>
<td>12</td>
<td>Ic1</td>
<td>A</td>
<td>\</td>
<td>\</td>
<td>1In</td>
<td>负载监控方式一</td>
</tr>
<tr>
<td>13</td>
<td>tc1</td>
<td>s</td>
<td>\</td>
<td>\</td>
<td>60s/80tr</td>
<td>负载监控方式一</td>
</tr>
<tr>
<td>14</td>
<td>Ic2</td>
<td>A</td>
<td>\</td>
<td>\</td>
<td>1In</td>
<td>负载监控方式二</td>
</tr>
<tr>
<td>15</td>
<td>tc2</td>
<td>s</td>
<td>\</td>
<td>\</td>
<td>60s/0.8tr</td>
<td>负载监控方式二</td>
<td></td>
</tr>
</tbody>
</table>
<p>负载监控方式一和负载监控方式二的默认值tc1和tc2的默认值根据不同类型的控制器判断,PTU4.1,4.2为60s,PTU6.2为80tr</p>
<p><strong>2.1控制器的电流不平衡保护tδ的默认值为5s。</strong></p>
<p><strong>PTU2.1控制器的Ig值需要特殊匹配;规则如下:</strong></p>
<table>
<thead>
<tr>
<th>额定电流</th>
<th>Ig</th>
</tr>
</thead>
<tbody>
<tr>
<td>630A</td>
<td>504A</td>
</tr>
<tr>
<td>800A</td>
<td>640A</td>
</tr>
<tr>
<td>1000A</td>
<td>800A</td>
</tr>
<tr>
<td>1250A</td>
<td>1000A</td>
</tr>
<tr>
<td>1600A</td>
<td>1120A</td>
</tr>
<tr>
<td>2000A</td>
<td>1200A</td>
</tr>
<tr>
<td>2500A</td>
<td>1000A</td>
</tr>
<tr>
<td>2900A</td>
<td>1160A</td>
</tr>
<tr>
<td>3200A</td>
<td>960A</td>
</tr>
<tr>
<td>3600A</td>
<td>1080A</td>
</tr>
<tr>
<td>4000A</td>
<td>1200A</td>
</tr>
<tr>
<td>5000A</td>
<td>1000A</td>
</tr>
<tr>
<td>6300A</td>
<td>1260A</td>
</tr>
</tbody>
</table>
<p><strong>说明:PTU4.1/PTU4.2/PTU6.1/PTU6.2型号的控制器Ig默认值:
计算0.8In值与1200A做比较取小值;tg默认值:根据表单字段-订单类型是风电光伏专用(3s)还是工业(0.8s)来确定默认值;
</strong></p>
<hr />
<p><strong>脱扣器类型:PT40-2L/PT40-M/PT40-2M/PT40-2H/PT40-3M/PT40-3H</strong></p>
<table>
<thead>
<tr>
<th>序号</th>
<th>字段名称</th>
<th>单位</th>
<th>下界</th>
<th>上界</th>
<th>默认值</th>
<th>上级字段</th>
</tr>
</thead>
<tbody>
<tr>
<td>1</td>
<td>Ir</td>
<td>A</td>
<td>0.4In</td>
<td>1In</td>
<td>1In</td>
<td>过载长延时保护</td>
</tr>
<tr>
<td>2</td>
<td>tr</td>
<td>s</td>
<td>8s</td>
<td>960s</td>
<td>60s</td>
<td>过载长延时保护</td>
</tr>
<tr>
<td>3</td>
<td>Isd</td>
<td>A</td>
<td>1.5Ir</td>
<td>15Ir</td>
<td>3Ir</td>
<td>短路短延时保护</td>
</tr>
<tr>
<td>4</td>
<td>Tsd</td>
<td>s</td>
<td>0.1s</td>
<td>0.4s</td>
<td>0.1s</td>
<td>短路短延时保护</td>
</tr>
<tr>
<td>5</td>
<td>Ii</td>
<td>A</td>
<td>1In</td>
<td>20In</td>
<td>5In</td>
<td>短路瞬时保护</td>
</tr>
<tr>
<td>6</td>
<td>Ig</td>
<td>A</td>
<td>0.2In</td>
<td>1In</td>
<td>0.8In/1200A</td>
<td>接地保护</td>
</tr>
<tr>
<td>7</td>
<td>tg</td>
<td>s</td>
<td>0.1s</td>
<td>100s</td>
<td>0.8/3s</td>
<td>接地保护</td>
</tr>
<tr>
<td>8</td>
<td>δ</td>
<td>A</td>
<td>0.5A</td>
<td>30A</td>
<td>0.5A</td>
<td>电流不平衡保护</td>
</tr>
<tr>
<td>9</td>
<td>tδ</td>
<td>s</td>
<td>0.006s</td>
<td>0.83s</td>
<td>3s</td>
<td>电流不平衡保护</td>
</tr>
<tr>
<td>10</td>
<td>Ic1</td>
<td>A</td>
<td>\</td>
<td>\</td>
<td>OFF</td>
<td>负载监控方式一</td>
</tr>
<tr>
<td>11</td>
<td>tc1</td>
<td>s</td>
<td>\</td>
<td>\</td>
<td>OFF</td>
<td>负载监控方式一</td>
</tr>
<tr>
<td>10</td>
<td>Ic2</td>
<td>A</td>
<td>\</td>
<td>\</td>
<td>OFF</td>
<td>负载监控方式二</td>
</tr>
<tr>
<td>11</td>
<td>tc2</td>
<td>s</td>
<td>\</td>
<td>\</td>
<td>OFF</td>
<td>负载监控方式二</td>
<td></td>
</tr>
</tbody>
</table>
<p><strong>PT40-2L控制器的Ig值需要特殊匹配;规则如下:</strong></p>
<table>
<thead>
<tr>
<th>额定电流</th>
<th>Ig</th>
</tr>
</thead>
<tbody>
<tr>
<td>630A</td>
<td>504A</td>
</tr>
<tr>
<td>800A</td>
<td>640A</td>
</tr>
<tr>
<td>1000A</td>
<td>800A</td>
</tr>
<tr>
<td>1250A</td>
<td>1000A</td>
</tr>
<tr>
<td>1600A</td>
<td>1120A</td>
</tr>
<tr>
<td>2000A</td>
<td>1200A</td>
</tr>
<tr>
<td>2500A</td>
<td>1000A</td>
</tr>
<tr>
<td>2900A</td>
<td>1160A</td>
</tr>
<tr>
<td>3200A</td>
<td>960A</td>
</tr>
<tr>
<td>3600A</td>
<td>1080A</td>
</tr>
<tr>
<td>4000A</td>
<td>1200A</td>
</tr>
<tr>
<td>5000A</td>
<td>1000A</td>
</tr>
<tr>
<td>6300A</td>
<td>1260A</td>
</tr>
</tbody>
</table>
<p><strong>说明:PT40-M/PT40-2M/PT40-2H/PT40-3M/PT40-3H型号的控制器Ig默认值:
计算0.8In值与1200A做比较取小值;tg默认值:根据表单字段-订单类型是风电光伏专用(3s)还是工业(0.8s)来确定默认值;
</strong></p>